Safety relay for failsafe controllers up to SILCL 3, Cat. 4, PL e, 1-channel operation, autostart, 1 enabling current path, US = 24 V DC in accordance with IEC 61131-6, fixed screw terminal block
Maximum power dissipation for nominal condition |
3.1 W (at US = 30 V, IL² = 36 A²) |
Nominal operating mode |
100% operating factor |
Air clearances and creepage distances between the power circuits |
Rated insulation voltage |
250 V AC |
250 V AC |
Rated surge voltage/insulation |
Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14)
Basic insulation 4 kV between all current paths and housing |
Supply |
Rated control circuit supply voltage US |
19.2 V DC ... 30 V DC |
Rated control circuit supply voltage US |
24 V DC -20 % / +25 % (at A1) |
Rated control supply current IS |
typ. 35 mA |
Power consumption at US |
typ. 840 mW |
Inrush current |
150 mA (Δt = 25 ms at Us) |
Filter time |
2.5 ms (at A1 in the event of voltage dips at Us) |
max. 3 ms (at A1; test pulse width; blanking pulses/dark test) |
1 s (at A1; test pulse rate; blanking pulses/dark test) |
Where test pulse width ≤ 1 ms: test pulse rate = 5 x test pulse width |
max. 1 ms (at A1; test pulse width; switch-on pulses/light test) |
100 ms (at A1; test pulse rate; switch-on pulses/light test) |
Unless switch-on pulses/light tests are safety-related, they should be disabled. |
Protective circuit |
Surge protection; Suppressor diode |
Protection against polarity reversal for rated control circuit supply voltage |